HomeHome Measurement ProductsProducts AboutAbout electrical measurement instruments contactContact
contact especialists electrical measurement [+34] 982 20 99 20
info@amperis.com
measurement instruments

Circuit breaker testers:
Technical Support

Models: POB30D

Testing the minimum trip voltage of high power circuit breakers

To ensure that circuit breaker operation is guaranteed under the most onerous conditions placed on the substation tripping supply, circuit breaker trip coils are specified to work with a minimum tripping voltage much below the nominal battery voltage. The minimum trip voltage test is described in a number of international and national standards such as IEC 56, ANSI C37.09 etc.

Traditionally, this test was performed by tapping the main tripping battery. This method however should not by utilised as it presents a considerable risk to testing personnel, battery and breaker being tested.

POB30D and POB30AD generate filtered DC voltage and it is developed for regular maintenance tests of power circuit breakers. It eliminates use of stationary batteries during testing. Output voltage is selectable from 10V to 300V DC.

Procedure steps:

Manual

  1. 1. Make certain that the mains are de-energized on both sides of the breaker, safety grounded and that local safety regulations are followed.
  2. 2. Ground the test instrument.
  3. 3. Connect Power box to the breakerīs opening circuit and spring-charging motor.
  4. 4. Switch the test instrument on.
  5. 5. Set the desired test voltage.
  6. 6. Activate the trip pulse switch.
  7. 7. Repeat steps 3 and 4 at a higher voltage if the circuit breaker does not trip.

Automatic

  1. 1. Make certain that the mains are de-energized on both sides of the breaker, safety grounded and that local safety regulations are followed
  2. 2. Ground the test instrument.
  3. 3. Connect Power box to the breakerīs opening circuit and spring-charging motor.
  4. 4. Switch the test instrument on.
  5. 5. Set the desired test voltages (minimal voltage, maximum voltage and step voltage).
  6. 6. Activate the trip pulse switch.
  7. 7. Wait until the coil is actuated. If the coil is not actuated, after 900msec of waiting time, voltage is automatically increased for a pre-selected step (value 1 to 19V), and the instrument repeats this procedure.

Test could have two possible outcomes: