info@amperis.com (+34) 982 20 99 20
Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: CAT III 300V acc. to EN 61010-1
- protection class acc. to EN 60529: IP54
Other technical data:
- power supply: alkaline batteries LR14 (C) (5 pcs.) or Ni-MH battery package
- charger power supply: 100...250V, 50...60Hz
- display: LCD, 20mm high
Rated operational conditions:
- operating temperature: 0...+40°C
- maximum interference voltage AC + DC, at which the measurement is still performed: 24V (68Vp-p)
- test current for resistance value ≤ 100Ω: 225mA
- maximum measured voltage: 40V
- test current frequency: 128Hz
Measurement of earthing resistance:
measurement range in accordance with IEC61557-5: 0,12Ω...20kΩ
| Range | Resolution | Accuracy |
| 0,00...9,99Ω | 0,01Ω | ±(3% m.v. + 3 digits) |
| 10,0...99,9Ω | 0,1Ω | ±(2% m.v. + 2 digits) |
| 100...999Ω | 1Ω | |
| 1,00...9,99kΩ | 0,01kΩ | |
| 10,0...20,0kΩ | 0,1kΩ |
Measurement of earthing resistance using clamps:
measurement range in accordance with IEC61557-5: 0,16Ω...20kΩ
| Range | Resolution | Accuracy |
| 0,00...9,99Ω | 0,01Ω | ±(8% m.v. + 3 digits) |
| 10,0...99,9Ω | 0,1Ω | ±(8% m.v. + 2 digits) |
| 100...999Ω | 1Ω | |
| 1,00...9,99kΩ | 0,01kΩ | |
| 10,0...20,0kΩ | 0,1kΩ |
Measurement of ground resistivity:
| Range | Resolution | Accuracy |
| 0,00...9,99Ωm | 0,01Ωm | ±(3% m.v. + 3 digits) |
| 10,0...99,9Ωm | 0,1Ωm | ±(2% m.v. + 2 digits) |
| 100...999Ωm | 1Ωm | |
| 1,00...9,99kΩm | 10Ωm | |
| 10,0...99,9kΩm | 100Ωm | |
| 100...999kΩm | 1kΩm |