Earth Resistance and Resistivity Meters MRU 105/106

MRU-105 meter
  • Measurement of earthing resistance using a three- or four- pole technique:
    - ability to perform measurements of multiple earthing system using three-pole
    technique without disconnecting earth system measured (with the application of clamps),
    - supervision of the measurement conditions (eg. voltages, impact resistance measurement electrodes RH i RS and battery state/monitor)
    - high immunity of interference voltage.
  • Measurement of ground resistivity (Wenner’s method):
    - the earth resistivity measurement with the possibility to introduce the distance between electrodes, automatic calculation and displaying the resistivity.
  • Measurement of resistance using a two- or four-pole technique.
  • Built-in battery charger.
  • Memory for 300 measurement results with an ability to transfer the data to a PC.
  • Meter meets the requirements of the standard EN 61557.

Electric security:
- type of insulation: double, according to  EN 61010-1 and IEC 61557
- measurement category: CAT III 300V acc. to EN 61010-1
- protection class acc. to EN 60529: IP54

Other technical data:
- power supply: alkaline batteries LR14 (C) (5 pcs.) or Ni-MH battery package
- charger power supply: 100...250V, 50...60Hz
- display: LCD, 20mm high

Rated operational conditions:
- operating temperature:     0...+40°C
- maximum interference voltage AC + DC, at which the measurement is still performed: 24V (68Vp-p)
- test current for resistance value ≤ 100Ω: 225mA
- maximum measured voltage: 40V
- test current frequency: 128Hz

Measurement of earthing resistance:
measurement range in accordance with IEC61557-5: 0,12Ω...20kΩ

 

Range Resolution Accuracy
0,00...9,99Ω 0,01Ω ±(3% m.v. + 3 digits)
10,0...99,9Ω 0,1Ω ±(2% m.v. + 2 digits)
100...999Ω
1,00...9,99kΩ 0,01kΩ
10,0...20,0kΩ 0,1kΩ

 

 

Measurement of earthing resistance using clamps:
measurement range in accordance with IEC61557-5: 0,16Ω...20kΩ

 

Range Resolution Accuracy
0,00...9,99Ω 0,01Ω ±(8% m.v. + 3 digits)
10,0...99,9Ω 0,1Ω ±(8% m.v. + 2 digits)
100...999Ω
1,00...9,99kΩ 0,01kΩ
10,0...20,0kΩ 0,1kΩ

 

 

Measurement of ground resistivity:

 

Range Resolution Accuracy
0,00...9,99Ωm 0,01Ωm ±(3% m.v. + 3 digits)
10,0...99,9Ωm 0,1Ωm ±(2% m.v. + 2 digits)
100...999Ωm 1Ωm
1,00...9,99kΩm 10Ωm
10,0...99,9kΩm 100Ωm
100...999kΩm 1kΩm