info@amperis.com (+34) 982 20 99 20
Additionally:
Electric security:
Rated operational conditions:
Other technical data:
Measurement of interference voltage
| Range | Resolution | Accuracy |
| 0...100V | 1V | ±(2% m.v. + 3 digits) |
Measurement of interference frequency
| Range | Resolution | Accuracy |
| 15...450Hz | 1Hz | ±(1% m.v. + 2 digits) |
Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC61557-5: 0,100Ω...19,9kΩ
| Range | Resolution | Accuracy |
| 0,000...3,999Ω | 0,001Ω | ±(2% m.v. + 4 digits) |
| 4,00...39,99Ω | 0,01Ω | ±(2% m.v. + 2 digits) |
| 40,0...399,9Ω | 0,1Ω | |
| 400...3999Ω | 0,001kΩ | |
| 4,00k...19,99kΩ | 0,01kΩ | ±(5% m.v. + 2 digits) |
Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC61557-4: 0,045Ω...19,99kΩ
| Range | Resolution | Accuracy |
| 0,000...3,999Ω | 0,001Ω | ±(2% m.v. + 4 digits) |
| 4,00...39,99Ω | 0,01Ω | ±(2% m.v. + 2 digits) |
| 40,0...399,9Ω |
0,1Ω |
|
| 400...3999Ω | 0,001kΩ | |
| 4,00k...19,99kΩ | 0,01kΩ | ±(5% m.v. + 2 digits) |
Measurement of resistance of auxiliary electrodes RH and RS
| Range | Range | Accuracy |
| 0...999Ω | 1Ω | ±(5% (RS+RE+RH) + 8 digits) |
| 1,00k...9,99kΩ | 0,01kΩ | |
| 10,0k...19,9kΩ | 0,1kΩ |
Measurement of multiple earthing resistance with using the clamp and auxiliary electrodes (3p + clamp) measurement range to IEC61557-5: 0,120Ω...1,99kΩ
| Range | Resolution | Accuracy |
| 0,000...3,999Ω* | 0,01Ω | ±(8% m.v. + 4 digits) |
| 10,0...99,9Ω | 0,01Ω | ±(8% m.v. + 3 digits) |
| 100...999Ω | 0,1Ω | |
| 1,00k...1,99kΩ | 1Ω |
* in range 0,000…0,045Ω the accuracy is not specified.
Measurement of multiple earthing resistance with using double clamps
| Range | Resolution | Accuracy |
| 0,00...19,99Ω | 0,1Ω | ±(10% m.v. + 3 digits) |
| 20,0...149,9Ω | 0,1Ω | ±(20% m.v. + 3 digits) |
Measurement of ground resistivity Measurement method: Wennera, ρ=2πLRE
| Range | Resolution | Accuracy |
| 0,0...199,9Ωm | 0,1Ωm | depending on measurement accuracy RE with 4p method, but not less than ±1 digit |
| 200...1999Ωm | 1Ωm | |
| 2,00k...19,99kΩm | 0,01kΩm | |
| 20,0k...99,9kΩm | 0,1kΩm | |
| 100k...999kΩm | 1kΩm |
L – distance between probes: 1...50m
Measurement of AC current (leakage)
| Range | Resolution | Accuracy |
| 0,1...99,9mA 1 | 0,1mA | ±(8% m.v. + 5 digits) |
| 100...999mA 1 | 1mA | ±(8% m.v. + 3 digits) |
| 1,00...4,99A 1,2 | 0,01A | ±(5% m.v. + 5 digits)1 unspecified 2 |
| 5,00...9,99A 1,2 | 0,01A | ±(5% m.v. + 5 digits) |
| 10,0...99,9A 1,2 | 0,1A | |
| 100...300A 1,2 | 1A |
1 – receiving clamp (diameter 52mm) – C-3
2 – flexible clamp (Rogowsky coil) with diameter 400 mm – F-1
Measurement of dynamic earthing resistance (RD) with impulse wave method (4p )
| Range | Resolution | Accuracy |
| 0,0...99,9Ω | 0,1Ω | ±(2,5% m.v. + 3 digits) |
| 100...199Ω | 1Ω |
choice impulse edges: 4/10ms, 10/350ms
„m.v.”- measured value
1955 €
Do you want to buy high quality Earth resistance and resistivity meters?
Inquire for our Earth resistance and resistivity meters prices.
Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20.We are happy to help you.