Insulation tester
Insulation tester MOH-5
- Insulation tester with double digital and analog indicator
- Reduced weight and size
- Measurement of current, frequency, continuity, and diodes
- Ability to program end of the insulation test
- Robust and compact design. Insulation tester very intuitive to operate
- Battery charge indicator
- Test voltages: 250 V, 500 V, and 1000 V
General
The MOH-5 insulation tester uses the most advanced electronics to host features that are not normally associated with more traditional insulation test equipment. The insulation tester has a large LCD screen with background light, which enhances the advantages of digital and analog indicators. The bar graph gives an instant idea of the measurement as if it were a needle in an analog instrument; this supplements the digital indicator, which shows the reading in a precise and unequivocal manner. With light and compact design, the MOH-5 insulation tester is a perfect combination of high performance and functionality.
Insulation tester OME-10
Features
- Analog measurement bar for making an immediate judgment.
- Auto-range and automatic turn-off features
- Last reading memory feature
- Feedback screen
- LCD 3 ¾ digit screen. Maximum reading 3999
- Timer feature for the insulation test. Ability to end automatically after 30 seconds
- Blocking feature for insulation test
Specifications
Medida de aislamiento- Range: 4000 MΩ
- Applied voltage: 250 V, 500 V, 1000 V
- Accuracy:
- ≤ 400 MΩ ± (3% + 5 digits)
- >400 MΩ y ≤ 400 MΩ ± (3% + 5 digits)
- >1000 MΩ ± (10% + 10 digits)
- Continuous voltage:
- Range: 1000 V dc
- Auto-range: 400mV/4V/40V/400V/1000V
- Accuracy:
- ≤m400V ± (1.5% + 5 digits)
- ≤400V ± (0.8% + 3 digits)
- > 400 V y ≤1000V (1% + 5 digits)
- Alternate voltage:
- Range: 750 V ac
- Auto-range: 400mV/4V/40V/400V/750V
- Accuracy:
- ≤400mV ± (1.5% + 5 digits)
- > 400 mV y ≤400V (1% + 5 digits)
- > 400 V y ≤750V (1.2% + 5 digits)
- Continuous current:
- Range: 400 mA
- Auto-range: 40 mA/400 mA
- Accuracy: ±(1.2%+3 digits)
- Alternate current:
- Range: 400 mA
- Auto-range: 40 mA/400 mA
- Accuracy: ±(1.5%+5 digits)
- Resistance:
- Range: 40 MΩ
- Ranges: 400 Ω /4kΩ /40kΩ /400kΩ /4MΩ /40MΩ
- Accuracy: ≤400 Ω ± (1% + 5 digits)
- > 400 Ω y ≤4 M Ω ±(1% + 3 digits)
- > 4 MΩ y ≤40 MΩ ±(1.8% + 5 digits)
- Frecuency
- Range: 100 kHz
- Accuracy: ±(0.8% + 3 digits)
- Diode test:
- Shows voltage drop
- Continuity test: A beep goes off if the resistance is below 30 Ω
- Insulation test:
- Range: 0.1 MΩ → 4000 MΩ
- Test voltages: 250 V, 500 V, 1000 V
- Accuracy of the test voltage: +20%, -0%
- Test nominal current (1 kΩ/V): 1 mA
- Alarm: In the insulation test, a beep goes off if the resistance is below 5 MΩ
| Range | 200 mΩ | 2 Ω | 20 Ω | 200 Ω | 2 kΩ | 20 kΩ |
| Precision | ±(0.5% + 1 digit) | |||||
| Test current | 100 mA | 100 mA | 10 mA | 10 mA | 1 mA | 0.1 mA |
| Resolution | 0.1 mΩ | 1 mΩ | 10 mΩ | 0.1 Ω | 1 Ω | 10 Ω |
| Test voltage | Range | Resolution | est cuurrent | Precision | ||
| 250 V | 0.1 → 400.0 MΩ | 0.1 MΩ | 1 mA @ 250 kΩ | ±(5%+5) | ||
| 400 → 1000.0 MΩ | 1 MΩ | |||||
| 1000.0 → 4000.0 MΩ | ±(10%+5) | |||||
| 500 V | 0.1 → 400.0 MΩ | 0.1 MΩ | 1 mA @ 500 kΩ | ±(5%+5) | ||
| 400 → 1000.0 MΩ | 1 MΩ | |||||
| 1000.0 → 4000.0 MΩ | ±(10%+5) | |||||
| 1000 V | 0.1 → 400.0 MΩ | 0.1 MΩ | 1 mA @ 1 MΩ | ±(5%+5) | ||
| 400 → 1000.0 MΩ | 1 MΩ | |||||
| 1000.0 → 4000.0 MΩ | ±(10%+5) | |||||
Accesories
- Test wires, batteries and manual