Insulation Resistance Meters MIC-5000
The most important features of MIC-5000 are:
- Insulation resistance measurement:
- test voltage selection between 250...5000V in 50V intervals, or predefined 250, 500, 1000, 2500, 5000V,
- on-line insulation resistance measurement or leakage current,
- automatic discharge of tested object’s capacitance after measurement of insulation resistance,
- direct measurement of one or two absorption coefficients,
- acoustic determination of 5 seconds time intervals that facilitates to take time characteristics during insulation resistance measurement,
- saving measured value of test voltages and selected times T1, T2 and T3 ranging from 1... 600 seconds,
- indicator of the actual test voltage value during a measurement,
- protection against live objects.
- AC/DC voltage measurement in range 0...600V.
- Memory for 999 measurement results with an ability to transfer the datato a PC.
- Automatic selection of measurement ranges.
- Powered by rechargeable battery pack:
- included with the device an external power supply for automatic battery charging to ensure prolonged battery life and optimal working conditions,
- battery status indicator.
- AUTO-OFF function.
- Meter meets the requirements of the standard EN 61557.
Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: CAT III 600V acc. to EN 61010-1
- measurement category for terminals and circuit 5kV: interpolated III 5000V
- protection class acc. to EN 60529: IP54
Rated operational conditions:
- operating temperature: -10...+50°C,
- test voltage accuracy (Robc[Ω]≥1000*Un[V]): -0...+10% of the set value,
- voltage fluctuation due to temperature changes better than: 0,2%/°C,
- converter output current:
- min. 1,0mA for rated test voltage
- 1,0...3,0mA for 2500V
- 1,0...1,4mA for 5000V
- measurement rate: approx. 1 measure/second
- quality standard: ISO 9001
Other technical data:
- power supply: Ni-MH battery pack
- power supply adaptor: 100...240V
- minimum measurement time 5kV/1mA according to EN 61557 (5s/25s) 5h or 600 measurements
- time to auto-off:
- mode RISO/IL depends on T2 or T3 (T2/T3 + 300 seconds) settings other modes 300 seconds
Insulation resistance measurement
- test voltage can be set in the range between 250V and 5000V with 50V intervals
- test voltage accuracy (Robc [Ω] ≥ 1000*UN [V]): 0 +10% of the set value
- voltage fluctuation due to temperature changes - better than 0,2% / °C
- measurement times T1, T2 i T3 for absorption coefficient measurement selected from the range between 1sec and 600sec with accuracy ± 1sec
measurement range according to PN-EN 61557-2: RISOmin...5,0TΩ; RISOmin=UISOnom/1mA
| Range |
Resolution |
Accuracy |
| 0,0...999,9kΩ |
0,1kΩ |
±(3% m.v. + 20 digits) |
| 1,000...9,999MΩ |
0,001MΩ |
| 10,00...99,99MΩ |
0,01MΩ |
| 100,0...999,9MΩ |
0,1MΩ |
| 1,000...9,999GΩ |
0,001GΩ |
| 10,00...99,99GΩ |
0,01GΩ |
| 100,0...999,9GΩ |
0,1GΩ |
| 1,000...5,000TΩ |
0,001TΩ |
for measurements of limited converter current, the accuracy is not specified.
Minimum insulation resistance measured without limited converter current
| Test voltage |
Range |
| 250V |
250kΩ |
| 500V |
500kΩ |
| 1000V |
1,0MΩ |
| 2500V |
2,5MΩ |
| 5000V |
5,0MΩ |
DC voltage measurement
| Range |
Resolution |
Accuracy |
| 0...600V |
1V |
±(3% m.v. + 2 digits) |
AC voltage measurement 50Hz (sinusoidal shape with harmonic contents < 2%)
| Range |
Resolution |
Accuracy |
| 0...600V |
1V |
±(3% m.v. + 2 digits) |
„m.v.” - measured value.
Leakage current reading
| Range |
Resolution |
Accuracy |
| 0...Ipmax |
depending on range |
-ΔI-, +ΔI+ |
Ipmax - maximum converter current 1,2 ± 0,2 mA, ΔI-, +ΔI+ - current reading accuracy calculated using the following formula:
UISO - test voltage R - displayed insulation resistance value ΔR - resistance measurement defined for a particular measurement