info@amperis.com (+34) 982 20 99 20
Insulation resistance measurement: 50, 100 250, 500 or 1000 V. 10GΩ ; Low voltage resistance measurement ; AC/DC voltage measurement 0...600V ; Capacitance measurements.
Continuity measurement of protective and equipotential conductors with the 200mA current |
||
Measuring range according to EN 61557-4: 0,10...1999Ω |
||
Range |
Resolution |
Accuracy |
0,00...19,99Ω |
0,01Ω |
±(2% m.v. + 3 digits) |
20,0...199,9Ω |
0,1Ω |
|
2000...1999Ω |
1Ω |
±(4% m.v. + 3 digits) |
Voltage on open terminals: <8V |
||
Output current at R <2Ω: ISC >200mA |
||
Compensation of test leads’ resistance |
||
Unidirectional current flow |
Low-voltage and resistance measurement |
||
Range |
Resolution |
Accuracy |
00,0...199,9Ω |
0,1Ω |
±(3% m.v. + 3 digits) |
2000...1999Ω |
1Ω |
|
Voltage on open terminals: <8V |
||
Current for closed terminals5mA < ISC << 15mA |
||
Sound signal and green LED on when measured resistance < 30Ω ± 50% |
||
Compensation of test leads’ resistance |
Capacitance measurements |
||
Range |
Resolution |
Accuracy |
1...999nF |
1nF |
±(5% m.v. +5 digits) |
1,00...9,99μF |
0,01μF |
|
Capacitance value displayed during the RISO measurement |
||
For test voltages below 100V and measured resistance below 10MΩ, unspecified capacitance measurement error |
||
Insulation resistance measurement: |
||
Measuring range according to EN 61557-2 for UN =50V: 50kΩ...250,0MΩ |
||
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
0,1kΩ |
±(3%.m.v. + 8 digits) |
1,000...9,999MΩ |
0,001MΩ |
|
10,0...99,99MΩ |
0,01MΩ |
|
100,0...250,0MΩ |
0,1MΩ |
Measuring range according to EN 61557-2 for UN =100V: 100kΩ...500,0MΩ |
||
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
0,1kΩ |
±(3%.m.v. + 8 digits) |
1,000...9,999MΩ |
0,001MΩ |
|
10,0...99,99MΩ |
0,01MΩ |
|
100,0...500,0MΩ |
0,1MΩ |
Measuring range according to EN 61557-2 for UN =250V: 250kΩ...2000,0MΩ |
||
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
0,1kΩ |
±(3%.m.v. + 8 digits) |
1,000...9,999MΩ |
0,001MΩ |
|
10,0...99,99MΩ |
0,01MΩ |
|
100,0..999,9MΩ |
0,1MΩ |
|
1000,0..2000,0MΩ |
1MΩ |
Measuring range according to EN 61557-2 for UN =500V: 500kΩ...5000,0MΩ |
||
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
0,1kΩ |
±(3%.m.v. + 8 digits) |
1,000...9,999MΩ |
0,001MΩ |
|
10,0...99,99MΩ |
0,01MΩ |
|
100,0..999,9MΩ |
0,1MΩ |
|
1000,0..5000,0MΩ |
1MΩ |
±(4%.m.v. + 6 digits) |
Measuring range according to EN 61557-2 for UN =1000V: 1000kΩ...10,0GΩ |
||
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
0,1kΩ |
±(3%.m.v. + 8 digits) |
1,000...9,999MΩ |
0,001MΩ |
|
10,0...99,99MΩ |
0,01MΩ |
|
100,0..999,9MΩ |
0,1MΩ |
|
1000,0..5000,0MΩ |
1MΩ |
±(4%.m.v. + 6 digits) |
5,0..10,0GΩ |
0,01GΩ |
Measurement of AC/DC voltage |
||
Range |
Resolution |
Accuracy |
0,0...299,9V |
0,1V |
±(2%m.v. + 6 digits) |
300...600V |
1V |
±(2%m.v. + 2 digits) |
Frequency range: 45...65Hz |
||
“m.v.” = “measured value”. |
AMIC-10 Specifications |
|
Electric security: |
|
Type of insulation |
Double, acc. to EN 61010-1 and IEC 61557 |
Measurement category |
CAT IV 600V acc. to EN 61010-1 |
Protection class acc. to EN 60529 |
IP67 |
Other technical data: |
|
Power suply |
4 alkaline batteries or battery package Ni-MH |
Weight |
1kg |
Dimensions |
220 x 100 x 60 mm |
Standard accesories:
Optional accesories:
Do you want to buy high quality Insulation resistance meters?
Inquire for our Insulation resistance meters prices.
Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20. We are happy to help you.