Insulation Resistance Meter AMIC-10k1

Insulation Resistance Meter AMIC-10k1

Insulation resistance measurement - 40TΩ: * 50 – 1000 V, 25 V steps, * 1000 – 10000 V, 50 V steps ; Memory, bluetooth keyboard (option), burnout location ; Capacitance and DC/AC voltage measurement ; Leakage current measurement ; Digital filters function ; Measurement of protective connections and equipotential bonding

Main characteristics are the following:

Insulation resistance measurement:

  • Measurement voltage:
    • *50 – 1000 V, 25 V steps
    • *1000 – 10000 V, 50V steps
  • Continuous indication of measured insulation resistance or leakage current
  • Automatic discharge of measured object capacitance voltage
  • Acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics
  • Metered T1 , T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s
  • Adjustable measuring time to 99'59'’,
  • Polarization index (PI) and dielectric absorption ratio (DAR) measurement
  • Indication of actual test voltage during measurement
  • 1.2 mA, 3mA and 5 mA test current
  • Insulation resistance measurement using two- or three-wire method
  • Measurements with test leads up to 20 m
  • Protection against measuring live objects
  • Measurement of capacitance during the measurement of RISO
  • Measurement of temperature (with additional probe - WASONT1)
  • Step voltage insulation resistance measurement (SV)
  • Dielectric Discharge calculation (DD)
  • Location of damage (burnout)
  • Digital filters function for measurements in high noise environment
  • Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557-4 with current > 200 mA
  • Adjustable limits for measured resistance RISO and RCONT
  • Measurement of leakage current during insulation resistance testing
  • DC and AC voltage measurement in the range of 0…750 V
  • Drawing graphs on the display during measurement
  • Innovative memory with possibility of description of: measurement points, facilities,…
  • Operating with mini Bluetooth keyboard (option)
  • Graphic LCD 5,6'’ backlit
  • Power supply from main power line or battery packs
  • Built-in fast charger

Measurement of capacitance

Range

Resolution

Accuracy

1...999 nF

1 nF

±(5%m.v. + 5 digits)

1,00...49.99 μF

0,01 μF

Capacity measurement result is displayed after the RISO measurement

For measuring voltages under 100 V capacitance measurement accuracy not specified

DC and AC voltage measurement

Range

Resolution

Accuracy

0,0...29.9 V

0,1 V

±(2%m.v. + 20 digits)

30,0...299.9 V

0,1 V

±(2%m.v. + 6 digits)

300...750 V

1 V

±(2%m.v. + 2 digits)

Frequency range: 45...65Hz

Insulation resistance measurement

Measurement range acc. to EN 61557-2:  5 M Ω ...20,0T Ω  (U N =5000V)

Range

Resolution

Accuracy

0,0...999,9kΩ

1kΩ

±(3%.m.v.. + 10 digits)

1,000...9,999MΩ

0,01MΩ

10,0...99,99MΩ

0,1MΩ

100,0...999,9MΩ

1MΩ

1,000...9,999GΩ

0,01GΩ

10,0...99,99GΩ

0,1GΩ

100,0...999,9GΩ

1GΩ

±(3,5%.m.v.. + 10 digits)

1,000...9,999TΩ

0,01TΩ

±(7,5%.m.v.. + 10 digits)

10,0...40,00TΩ

0,1TΩ

±(12,5%.m.v.. + 10 digits)

Values of measured resistance depending on measurement voltage

Voltage UISO

Measurement range

Measurement range (AUTOISO-5000)

50V

200GΩ

20GΩ

100V

400GΩ

40GΩ

250V

1,00TΩ

100GΩ

500V

2,00TΩ

200GΩ

1000V

4,00TΩ

400GΩ

2500V

10,00TΩ

400GΩ

5000V

20,00TΩ

400GΩ

10000V

40,00TΩ

----

Continuity measurement of protective connections and equipotential bonding,I=200mA

Range

Resolution

Accuracy

0.00...19.99 Ω

0.01 Ω

±(2%m.v. + 3 digits)

20.0...199.9 Ω

0.1 Ω

200...999 Ω

1 Ω

±(4%m.v. + 3 digits)

Voltage on open terminals: 4...24 V

Output current at R <15 Ω: min. 200 mA (ISC : 200...250 mA)

Compensation of test lead resistance

Current flowing in both directions, mean value of resistance is displayed

Measurement of temp

Range

Resolution

Accuracy

-40,0...99,9 °C

1 °C

±(3%m.v. + 8 digits)

-40,0...211,8 °F

1 °F

±(3%m.v. + 16 digits)

“m.v.” = “measured value”.

SpecificationsAMIC-10k1

Electric security:

Type of insulation

Double, acc. to EN 61010-1 and IEC 61557

Measurement category

CAT IV 600V (III 1000V) EN 61010-1

Protection class acc. to EN 60529

IP40 (IP67 with cover closed)

Other technical data:

Power supply

90 – 265V 50/60Hz and built-in battery packs

Weight

aprox. 7 kg

Dimensions

390 x 310 x 180 mm

Display

LCD de 5,6”

Transmission of measurement results

USB or Bluetooth

Standard accesories:

  • test lead banana plug; 3 m; 10kV; red
  • test lead banana plug; 3 m; 10 kV; blue
  • test lead banana plug; 1,8 m; 10 kV; black; shielded
  • USB cable
  • “crocodile" clip 5,5 kV; black
  • “crocodile" clip 5,5 kV; blue
  • “crocodile" clip 5,5 kV; red
  • pin probe 10 kV with banana connector; red
  • pin probe 10 kV with banana connector; black
  • carrying case L4 for accesories
  • power cord
  • battery pack (built-in)
  • Software
  • calibration certificate

Do you want to buy high quality Insulation resistance meters?

Inquire for our Insulation resistance meters prices.

Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20. We are happy to help you.