Insulation Resistance Meter AMIC-2

Insulation Resistance Meter AMIC-2

Digital insulation meter AMIC-2 selects automatically insulation measurements range at 250 and 500 V test voltages. This insulation meter is suited for insulation resistance measurements of electric installations, motors and other electric devices. AMIC-2 can also be used to measure voltage up to 600 V AC and resistance up to 1999. Instrument is easy to use, professional tool in small and incredibly ergonomic case.

Main characteristics are the following:

  • Insulation resistance measurement:
  • Measurement voltage is selected between the two values 250 V or 500 V
  • On-line insulation resistance measurement
  • Automatic discharge of tested object’s capacitance after measurement of insulation resistance,
  • Acoustic determination of 5 seconds time intervals that facilitates to take time
  • Low voltage resistance measurement in range 0...2000Ω:
  • Current measurement <10 mA with resolution 0.1Ω,
  • Quick acoustic signalling (beeper) for circuit resistance below 10 Ω.
  • AC/DC voltage measurement in range 0...600V:
  • Automatic detection AC/DC voltaje
  • Autoranging
  • Suitable for 50 Hz and 60 Hz network
  • Backlit display
  • AUTO-OFF function
  • Meter meets the requirements of the standard EN 61557

Insulation resistance measurement:

UISO =250V

Measurement range according to IEC 61557-2: 250kΩ...1000MΩ

Range

Resolution

Accuracy

1...249kΩ

1kΩ

not specified

250...1999kΩ

1kΩ

±(3%.m.v.. + 8 digits)

2,00...19,99MΩ

0,01MΩ

20,0...199,9MΩ

0,1MΩ

200...1000MΩ

1MΩ

UISO =500V

Measurement range according to IEC 61557-2: 500kΩ...1000MΩ

Range

Resolution

Accuracy

1...499kΩ

1kΩ

No definido

500...1999kΩ

1kΩ

±(3%.m.v.. + 8 digits)

2,00...19,99MΩ

0,01MΩ

20,0...199,9MΩ

0,1MΩ

200...1999MΩ

1MΩ

Resistance measurement:

Range

Resolution

Accuracy

0,0...199,9Ω

0,1Ω

±(4% m.v. + 3 digits)

200...1999Ω

Continuous audible signal for R < 10 Ω

Measurement current (with open terminals for Ubat > 3.0 V): < 10 mA

Max voltage on open terminals: 4...24 V

Max interference voltage for which measurement is still possible: +7 V/-1 V DC, 5 V AC

AC/DC voltage measurement

Range

Resolution

Accuracy

0...600V

1V

±(3% m.v. + 2 digits)

“m.v.” = “measured value”.

AMIC-2 Specifications

Electric security:

Type of insulation

Double, acc. to EN 61010-1 and IEC 61557

Measurement category

CAT IV 600V acc. to EN 61010-1

Protection class acc. to EN 60529

IP65

Other technical data:

Power supply

Batteries LR03 (AAA) (2 pcs.) or rechargeable battery

Measurement current RISO

1,2mA ± 0,2mA

Max interference voltage at which a measurement is realice  RISO

20V

Number of RISO measurements

> 500

Dimensions

approx. 240x60x30 mm

Weight

approx. 0,3kg

Auto power-off

5 min.

Electromagnetic compatibility

According to EN 61000-6-3 and EN 61000-6-2

Standard accesories:

  • Cocodrile clip K01; black
  • Pin probe with banana connector; black
  • Batteries 1,5V (AAA) (2 pcs.)
  • Calibration certificate
  • Operating manual

Optional accesories:

  • AGT-16P triple phase socket adapter
  • AGT-32P triple phase socket adapter
  • AGT-63P triple phase socket adapter
  • Carrying case S2
  • Calibration certificate by calibration laboratory
Using Insulation Resistance Meter AMIC-2Examples of use of Insulation Resistance Meter AMIC-2

Do you want to buy high quality Insulation resistance meters?

Inquire for our Insulation resistance meters prices.

Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20. We are happy to help you.