info@amperis.com (+34) 982 20 99 20
Insulation resistance measurement - 15TΩ: * 50 – 1000 V, 10 V steps, * 1000 – 5000 V, 25 V steps ; Memory of 999 measurement results and PC transmission ; Capacitance and DC/AC voltage measurement ; Leakage current measurement ; Digital filters function ; Measurement of protective connections and equipotential bonding
Measurement of capacitance |
||
Range |
Resolution |
Accuracy |
1...999 nF |
1 nF |
±(5%m.v. + 5 digits) |
1,00...49.99 μF |
0,01 μF |
|
Capacity measurement result is displayed after the RISO measurement |
DC and AC voltage measurement |
||
Range |
Resolution |
Accuracy |
0,0...29.9 V |
0,1 V |
±(2%m.v. + 20 digits) |
30,0...299.9 V |
0,1 V |
±(2%m.v. + 6 digits) |
300...600 V |
1 V |
±(2%m.v. + 2 digits) |
Frequency range: 45...65Hz |
||
“m.v.” = “measured value”. |
Insulation resistance measurement |
||
Measurement range acc. to EN 61557-2: 50 kΩ...15,0TΩ (I ISOnom =1,2 mA ó 3 mA) |
||
Range |
Resolution |
Accuracy |
0,0...999,9kΩ |
1kΩ |
±(3%.m.v.. + 10 digits) |
1,000...9,999MΩ |
0,01MΩ |
|
10,0...99,99MΩ |
0,1MΩ |
|
100,0...999,9MΩ |
1MΩ |
|
1,000...9,999GΩ |
0,01GΩ |
|
10,0...99,99GΩ |
0,1GΩ |
|
100,0...999,9GΩ |
1GΩ |
±(3,5%.m.v.. + 10 digits) |
1,000...9,999TΩ |
0,01TΩ |
±(7,5%.m.v.. + 10 digits) |
10,0...15,00TΩ |
0,1TΩ |
±(10%.m.v.. + 10 digits) |
Values of measured resistance depending on measurement voltage |
|
Voltage UISO |
Measurement range |
250V |
500GΩ |
500V |
1,00TΩ |
1000V |
2,00TΩ |
2500V |
5,00TΩ |
5000V |
15,00TΩ |
Measurement of leakage current |
||
Range |
Resolution |
Accuracy |
0…1,2 mA* |
Resolution and units result from the measurement range of individual insulation resistance |
Calculated basing on resistance measurements |
0…3 mA* |
||
* - depending on the setting |
Step voltage insulation resistance measurement |
|
Target voltage |
Measurement voltage sequence |
1 kV |
200, 400, 600, 800, 1000 V |
2.5 kV |
0.5, 1, 1.5, 2, 2.5 kV |
5 kV |
1, 2, 3, 4, 5 kV |
Duration of each "step" adjustable from 30 s to 5 mins |
|
Measurement result for each voltage step is stored in memory |
Continuity measurement of protective connections and equipotential bonding,I=200mA |
||
Range |
Resolution |
Accuracy |
0.00...19.99 Ω |
0.01 Ω |
±(2%m.v. + 3 digits) |
20.0...199.9 Ω |
0.1 Ω |
|
200...999 Ω |
1 Ω |
±(4%m.v. + 3 digits) |
Voltage on open terminals: 4...24 V |
||
Output current at R <15 Ω: min. 200 mA (ISC : 200...250 mA) |
||
Compensation of test lead resistance |
||
Current flowing in both directions, mean value of resistance is displayed |
Specifications AMIC-5010 |
|
Electric security: |
|
Type of insulation |
Double, acc. to EN 61010-1 and IEC 61557 |
Measurement category |
CAT IV 600V (III 1000V) EN 61010-1 |
Above sea level |
3000 m. |
Protection class acc. to EN 60529 |
IP54 (IP67 with cover closed) |
Other technical data: |
|
Power supply |
90 – 265V 50/60Hz and built-in battery packs |
Weight |
aprox. 7 kg |
Dimensions |
390 x 310 x 170 mm |
Display |
LCD |
Measurement results memory |
990 cells of memory (11880 records) |
Transmission of measurement results |
USB or wireless interface |
Standard accesories:
Optional accesories:
Do you want to buy high quality Insulation resistance meters?
Inquire for our Insulation resistance meters prices.
Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20. We are happy to help you.