Electric security:
Other technical data:
Rated operational conditions:
Leakage current reading
Range | Resolution | Accuracy |
0...Ipmax | depending from range | -ΔI-, +ΔI+ |
Ipmax - maximum converter’s current equal to 1,2 ± 0,2 mA,
ΔI-, +ΔI+ - current reading accuracy calculated from the resistance reading using the formulas:
UISO - test voltage
R - displayed value of the insulation resistance
ΔR - resistance measurement accuracy defined for the measurement
Insulation resistance measurement
measurement range to EN 61557-2: RISOmin = UISOnom/IISOmax…110,0 GΩ
IISOmax = 1mA
Range | Resolution | Accuracy |
0,00..99,99kΩ | 0,01kΩ | ±(3% m.v. + 20 digits) |
100,0..999,9kΩ | 0,1kΩ | |
1,000..9,999MΩ | 0,001MΩ | |
10,00..99,99MΩ | 0,01MΩ | |
100,0..999,9MΩ | 0,1MΩ | |
1,000..9,999GΩ | 0,001GΩ | |
10,00..99,99GΩ | 0,01GΩ | |
100,0..110,0GΩ | 0,1GΩ |
for measurements of limited converter current, the accuracy is not specified.
Low voltage resistance measurement
Range | Resolution | Accuracy |
0,0...99,9Ω | 0,1Ω | ±(2% m.v. + 3 digits) |
100,0...399,9Ω | 0,1Ω | ±(4% m.v. + 3 digits) |
acoustic signalling for resistance below 35Ω ± 25Ω
max. voltage on the open terminals - 9,6 V
current with the closed terminals - 200mA
DC voltage measurement
Range | Resolution | Accuracy |
0...600V | 1V | ±(3% m.v. + 2 digits) |
AC voltage measurement
50Hz (sinusoidal shape with harmonic contents < 2%)
Range | Resolution | Accuracy |
0...600V | 1V | ±(3% m.v. + 2 digits) |
„m.v.” - measured value.
440 €
Do you want to buy high quality Insulation resistance meters?
Inquire for our Insulation resistance meters prices.
Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20. We are happy to help you.