info@amperis.com (+34) 982 20 99 20
Multimeter ACMM-10 has been designed for the purpose of measurements of AC/DC voltage, AC/DC current, resistance, capacitance, frequency, duty cycle, temperature and also for testing diodes and continuity.
Frequency measurement(“m.v.”- measured value) |
|
Resolution |
Accuracy |
0,001 Hz |
±(1,5% m.v. + 5 digits) |
0,01 Hz |
|
0,1 Hz |
±(1,2% m.v. + 3 digits) |
0,001 kHz |
|
0,01 kHz |
|
0,1 kHz |
|
0,001 MHz |
±(1,5% m.v. + 4 digits) |
0,01 MHz |
|
· sensitivity: ≥8V RMS |
Duty cycle measurement |
||
Range |
Resolution |
Accuracy |
0,1...99,9% |
0,1% |
±(1,2% m.v. + 2 digits) |
· sensitivity: ≥8V RMS |
||
· pulse width: 100μs - 100ms |
||
· frequency width: 5Hz...150kHz |
Temperature measurement |
||
Range |
Resolution |
Accuracy * |
-20°C...+760°C |
1°C |
±(3% m.v. + 5°C, 9°F) |
-4°F...+1400°F |
1°F |
|
*) probe (K type) accuracy not included |
Capacitance measurement |
||
Range |
Resolution |
Accuracy |
40,00 nF |
0,01 nF |
±(5,0% m.v. + 7 digits) |
400,0 nF |
0,1 nF |
±(3,0% m.v. + 5 digits) |
4,000 µF |
0,001 μF |
|
40,00 µF |
0,01 μF |
|
100,0 µF |
0,1 μF |
±(5,0% m.v. + 5 digits) |
Resistance measurement |
||
Range |
Resolution |
Accuracy |
400,0 Ω |
0,1 Ω |
±(1,2% m.v. + 4 digits) |
4,000 kΩ |
0,001 kΩ |
±(1,0% m.v. + 2 digits) |
40,00 kΩ |
0,01 kΩ |
±(1,2% m.v. + 2 digits) |
400,0 kΩ |
0,1 kΩ |
|
4,000 MΩ |
0,001 MΩ |
|
40,00 MΩ |
0,01 MΩ |
±(2,0% m.v. + 3 digits) |
DC voltage measurement |
||
Range |
Resolution |
Accuracy |
400,0 mV |
0,1 mV |
±(0,5% m.v. + 2 digits) |
4,000 V |
0,001 V |
±(1,5% m.v. + 2 digits) |
40,00 V |
0,01 V |
|
400,0 V |
0,1 V |
|
600 V |
1 V |
±(1,5% m.v. + 2 digits) |
· input impedance: 7,8 MΩ |
AC voltage measurement |
||
Range |
Resolution |
Accuracy |
400,0 mV |
0,1 mV |
±(1,5% m.v. + 2 digits) |
4,000 V |
0,001 V |
±(1,2% m.v. + 3 digits) |
40,00 V |
0,01 V |
±(1,5% m.v. + 3 digits) |
400,0 V |
0,1 V |
|
600 V |
1 V |
±(2,0% m.v. + 4 digits) |
· input impedance: 7,8 MΩ |
||
· frequency range: 50...400Hz. |
DC current measurement |
||
Range |
Resolution |
Accuracy |
400,0 µA |
0,1 µA |
±(1,0% m.v. + 3 digits) |
4 000 µA |
1 μA |
±(1,5% m.v. + 3 digits) |
40,00 mA |
0,01 mA |
|
400,0 mA |
0,1 mA |
|
4,000 A |
0,001 A |
±(2,5% m.v. + 5 digits) |
10,00 A |
0,01 A |
|
AC current measurement |
||
Range |
Resolution |
Accuracy |
400,0 µA |
0,1µA |
±(1,5% m.v. + 5 digits) |
4 000 µA |
1 μA |
±(1,8% m.v. + 5 digits) |
40,00 mA |
0,01 mA |
|
400,0 mA |
0,1 mA |
|
4,000 A |
0,001 A |
±(3,0% m.v. + 7 digits) |
10,00 A |
0,01 A |
|
· frequency range: 50...400Hz. |
ACMM-10 Specifications |
|
Electric security: |
|
Type of insulation |
Double, according to EN 61010-1 and IEC 61557 |
Measurement category |
CAT II 600V acc. to EN 61010-1:2004 |
Protection class acc. to EN 60529 |
IP40 |
Other technical data: |
|
Power supply |
9V battery type 6LR61 |
Diode test |
I=0,3mA, U =1,5V DC |
Continuity test |
I<0,3mA, sound signal for R<50Ω |
Over range indication |
0L displayed |
Sampling rate |
2 times per second |
Input impedance |
7,8MΩ (V AC/DC) |
Display |
5000 counts LCD display with function indication |
Dimensions |
138 x 68 x 37 mm |
Weight |
approx. 210 g |
Fuses |
mA, μA range: 0,5A/250V fast |
Auto power OFF |
30 min |
Accordance with following standards |
EN 61010-1:2004 |
Quality standard |
ISO 9001 |
Rated operational conditions: |
|
Operating temperature |
0...+50°C at <70% rel. humidity |
Storage temperature |
-20...+60°C at <80% rel. humidity |
Standard accesories:
Optional accesories:
Do you want to buy high quality Multimeters?
Inquire for our Multimeters prices.
Do not hesitate to contact us, call us today by phone (+34) 982 20 99 20. We are happy to help you.