Vacuum Bottle Testers HVBT-75

Vacuum Bottle Testers Amperis HVBT-75

The HVBT-75 is microprocessor-based, portable, dc 75 kV vacuum bottle testers. These lightweight, portable testers are designed for testing circuitbreaker vacuum bottles in the field and at the shop.

Test voltages can be selected from 10 kV dc to 75 kV dc in 5 kV steps. The high-voltage test time can be set from 5 seconds to 2 minutes. The test voltage is raised to the selected voltage and held for the test time duration. After the test time duration has elapsed and the leakage current did not pass the preset value of 100 μA, 200 μA, or 300 μA, the test voltage is returned to zero. If a flash-over condition occurs, such as bottle failure, the test voltage is immediately turned off, a “Failure” message is displayed on the LCD screen, and the “TEST FAIL” LED light on the unit is also illuminated.

The presence of high voltage is indicated by an audible tone and an illuminated “HIGH VOLTAGE” LED light. For additional operator safety, an “ARM” switch must be held down during testing.

The HVBT-75 feature a back-lit LCD screen (16 characters by 2 lines) that is viewable in both bright sunlight and low-light levels. A turn-and-press knob is used to control the unit. An RS-232C interface port is provided for factory calibration and diagnostic testing.

Each unit is furnished with a 10-foot test cable that is terminated with a quick disconnect test clip. A transportation case is also included.

HVBT-75’s Specifications

Type

HVBT-75: portable, lightweight, 75 kV dc vacuum bottle tester

Physical specifications

17"W x 10K"H x 3K"D (42.7 cm x 26.9cm x 8.9 cm); Weight: 10 lbs (4.53 kg)

Input power

2 amps, 90 - 240 Vac, 50/60 Hz

Output voltage

HVBT-75: 10kV - 75 kV dc in 5 kV steps; accuracy: 1.5%

Output ripple voltage

3% max

Discharge time

Maximum discharge time for internal high voltage is 3 seconds

Display

Back-lit LCD Screen (16 characters by 2 lines); viewable in bright sunlight and low-light levels

Failure indicator

Failure indicator LED illuminates when test current exceeds 100 μA, 200 μA, 300 μA (programmable)

Control

Single turn-and-press knob

Computer interface

RS-232C port for factory calibration and diagnostics

Environment

Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)

Humidity

90% RH @ 40°C (104°F) non-condensing

Altitude

2,000 m (6,562 ft) to full safety specifications

Cables

One 10-foot high-voltage cable, one 10-foot high voltage return cable, one ground cable, one power cord

Transportation case

Transportation case is included

Warranty

1 year on parts and labor

NOTE: the above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice