Transformers Testing 3PHASE

Transformers Testing 3PHASE

The 3-PHASE is a true three-phase transformer turns-ratio tester designed to conform to the IEEE C57.12.90 measurement standard. The 3-PHASE generates and outputs a three-phase excitation test voltage to the three transformer primary windings. The induced three-phase secondary voltages are sensed, and the transformer turns-ratio is calculated. The 3-PHASE can measure turns-ratios from 0.8 to 15,000. The three phase turns-ratios, excitation current, and phase angle readings are displayed on the unit’s LCD screen. Since a three-phase voltage is used to excite the transformer windings, the 3-PHASE can detect and measure turns-ratios of any transformer type, including phase-shifting transformers.

The 3-PHASE can be used as a stand-alone unit or can be computer-controlled. It can be operated locally using its alpha-numeric keypad and rotary switch. Information is displayed on a back-lit LCD screen (128 x 64 pixels) that is viewable in both bright sunlight and low-light levels. Test reports can be printed in the field on the unit’s built-in 4.5-inch wide thermal printer. The 3-PHASE can store up to 112 test records and 128 test plans in Flash EEPROM. Test records or test plans can be stored or transferred to and from a PC via the available interfaces (RS-232C port, USB port, USB Flash drive port).

Transformer Test Voltages

The 3-PHASE generates three-phase transformer test voltages from a single-phase AC or DC power source. Three test voltages (8 Vac, 40 Vac, 100 Vac) allow the 3-PHASE to test CT’s and PT’s, as well as power transformers.

Auto-Detect Transformer Configuration

The 3-PHASE can automatically detect 130 different transformer types defined by ANSI, CEI/ IEC, and Australian standards, as well as phase shifting transformers.

Internal Test Record Storage

Up to 112 test records can be stored in the 3-PHASE’s Flash EEPROM. Each test record may contain up to 99 turns-ratio, excitation current, phase angle, and nameplate voltage readings. Test records can be recalled locally or transferred to a PC via the available interfaces (RS-232C port, USB port, USB Flash drive port).

Built-in Thermal Printer

The 3-PHASE features a convenient built-in 4.5- inch wide thermal printer that can be used to print test results.

Transformer Test Plans

The 3-PHASE can store up to 128 transformer test-plans in its Flash EEPROM. A test-plan is comprised of the transformer nameplate voltages for each tap setting. The calculated turns-ratio based on the nameplate voltages is compared with the measured turns-ratio to derive the percentage error and Pass/Fail results. By recalling a test plan, a transformer can be quickly tested and turns-ratio Pass/Fail reports can be reviewed. Test plans can be created with the PC software and can be transferred to the 3-PHASE via the available interfaces (RS-232C port, USB port, USB Flash drive port).

User Interface

The 3-PHASE features a back-lit LCD screen (128 x 64 pixels) that is viewable in both bright sunlight and low-light levels. The test results screen displays the transformer turns-ratio, excitation current, phase angle, and percentage error. The unit is controlled via a rugged, 16-key, membrane keypad and a digital rotary switch.

USB Flash Drive Interface

A built-in USB Flash drive interface provides a convenient method for transferring test plans and test records to or from a USB Flash drive. The user can store up to 999 transformer test plans and test records on a USB Flash drive, and the supplied PC software can be used to view the test records.

Computer Interface

The 3-PHASE can be computer-controlled via he RS-232C or USB port using the Windows®- based Transformer Turns-Ratio Analyzer Series 2 (TTRA S2) software provided with each 3-PHASE. The software can be used to run a test and to store test results on a PC. Test results can also be exported to Excel, PDF, and XML formats for further analysis.

Input Power Sources

The 3-PHASE can be powered from a single phase 100-240 Vac 50/60 Hz power source. A built-in safety ground detection circuit can detect and display any ground fault problems with the AC input source.

Transformer Load Tap Changer Control

Voltage regulator or LTC tap positions can be changed remotely using the unit’s built-in transformer load tap changer. This feature eliminates the need to manually raise or lower tap positions from the transformer control panel.

3-PHASE's Specifications

Type

True, 3-phase transformer turns ratio tester

Physical specifications

21”W x 9”H x 17”D (53 cm x 24 cm x 43 cm ); Weight: 35 lbs (15.8 kg)

Input power

3 amps, 100 - 240 Vac, 50/60 Hz

Measurement method

ANSI/IEEE C57.12.90

Ratio measuring range

0.8 - 15,000 (5-digit resolution)

Turns ratio accuracy

0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 8 Vac
0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 40 Vac
0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 100 Vac

Test voltages

Three-phase, 8 Vac @ 1 Amp, 40 Vac @ 0.2 Amps, 100 Vac @ 0.1 Amp

Excitation current reading range

0 - 2 Amperes; Accuracy: ±1mA, ±2% of reading (±1 mA)

Phase angle measure

0 - 360 degrees; Accuracy: ±0.2 degrees ( ±1 digit)

Display

Back-lit LCD screen (128 x 64 pixels) viewable in bright sunlight and low-light levels

Printer

Built-in 4.5-inch wide thermal printer

Computer interface

One RS-232C port, one USB port

External data storage

One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included)

Pc software

Windows®-based Transformer Turns-Ratio Analyzer application is included

Internal test record storage

Can store 112 transformer test records internally. Each record holds the test record header and up to 99 readings.

Internal test plan storage

Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via the RS-232C/USB port or via the USB Flash drive interface

Load tap changer contact

240 Vac, 1 Amps

Safety

Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards

Environment

Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)

Humidity

90% RH @ 40°C (104°F) non-condensing

Altitude

2,000 m (6,562 ft) to full safety specifications

Cables

One 15-foot single-phase set, one 15-foot three-phase set, one 25-foot extension set, one ground cable, one USB cable, one RS-232C cable, power cord, cable bag

Optional accessories

Transportation case

Warranty

1 year on parts and labor

NOTE:the above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice

Connections Transformers Testing 3PHASETest results Transformers Testing 3PHASEControls Transformers Testing 3PHASE